Main Code
|
Suffix Codes
|
Description
|
266HSH
|
|
|
|
|
|
Gauge Pressure Transmitter with remote seal– BASE ACCURACY 0.06%
|
SENSOR - Span limits
|
E
|
|
|
|
|
0.54 and 16kpa,5.4 and 160mbar,2.16 and 64inH2o
|
F
|
|
|
|
|
0.4 and 40kpa,4 and 400mbar,1.6 and 160inH2o
|
H
|
|
|
|
|
1.6 and 160kpa,16 and 1600mbar,6.4 and 642inH2o
|
M
|
|
|
|
|
6 and 600kpa,0.06 and 6bar,0.87 and 87psi
|
P
|
|
|
|
|
24 and 2400kpa,0.24 and 24bar,3.5 and 348psi
|
Q
|
|
|
|
|
80 and 8000kpa, 0.8 and 80bar,11.6 and 1160psi
|
S
|
|
|
|
|
160 and 16000kpa,1.6 and 160bar,23.2 and 2320psi
|
W
|
|
|
|
|
1400 and 70000kpa,14 and 700bar,203 and 10150psi
|
Z
|
|
|
|
|
10500 and 105000kpa,105 and 1050bar,1522 and 15225psi
|
Diaphragm material , Fill fluid (wetted parts)
|
|
S
|
|
|
|
ANSI 316L SS, Silicone oil, NACE
|
|
K
|
|
|
|
Hastelloy C276, Silicone oil, NACE
|
|
M
|
|
|
|
Monel 400, Silicone oil, NACE
|
|
8
|
|
|
|
ANSI 316L SS gold plated, Silicone oil, NACE
|
|
T
|
|
|
|
Tantalum , Silicone oil, NACE
|
|
A
|
|
|
|
ANSI 316L SS, Inert fluid - Galden, NACE
|
|
F
|
|
|
|
Hastelloy C276, Inert fluid - Galden, NACE
|
|
C
|
|
|
|
Monel 400, Inert fluid - Galden, NACE
|
|
9
|
|
|
|
ANSI 316L SS gold plated, Inert fluid - Galden, NACE
|
|
D
|
|
|
|
Tantalum , Inert fluid - Galden, NACE
|
|
L
|
|
|
|
ANSI 316L SS, Inert fluid - Halocarbon, NACE
|
|
P
|
|
|
|
Hastelloy C276, Inert fluid - Halocarbon, NACE
|
|
4
|
|
|
|
Monel 400, Inert fluid - Halocarbon, NACE
|
|
I
|
|
|
|
Monel 400, Inert fluid - Halocarbon, NACE
|
|
5
|
|
|
|
ANSI 316L SS gold plated, Inert fluid - Halocarbon, NACE
|
|
N
|
|
|
|
Inconel 718, no filling
|
Process connection (wetted parts)
|
|
|
B
|
|
|
ANSI 316L SS, 1/2"-14NPT female, NACE
|
|
|
T
|
|
|
ANSI 316L SS, 1/2"-14NPT male, NACE
|
|
|
P
|
|
|
ANSI 316L SS, DIN EN837-1 G 1/2 B
|
|
|
A
|
|
|
ANSI 316L SS, adaptor straight (180 °)entry(not available with bracket)
|
|
|
N
|
|
|
ANSI 316L SS, adaptor straight 90 °entry
|
|
|
E
|
|
|
Hastelloy C-276 ,1/2"-14NPT female
|
|
|
K
|
|
|
Hastelloy C-276 ,1/2"-14NPT male
|
|
|
D
|
|
|
Hastelloy C-276, DIN EN837-1 G 1/2 B
|
|
|
F
|
|
|
Hastelloy C-276, adaptor straight (180 °)entry(not available with bracket)
|
|
|
C
|
|
|
Hastelloy C-276, adaptor straight 90 °entry
|
|
|
1
|
|
|
Model 400, 1/2"-14NPT female
|
|
|
2
|
|
|
Model 400, 1/2"-14NPT male
|
|
|
3
|
|
|
Model 400, DIN EN837-1 G 1/2 B
|
|
|
6
|
|
|
Inconel 718,F250C(for sensor Z ONLY)
|
|
|
7
|
|
|
Inconel 718, 1/4"-18NPT female(for sensor Z ONLY)
|
Housing material and electrical connection
|
|
|
|
A
|
|
Aluminum alloy ( barrel version), 1/2"-14NPT
|
|
|
|
B
|
|
Aluminum alloy ( barrel version), M20*1.5(CM20)(To BE USED for WirelessHART)
|
|
|
|
S
|
|
ANSI 316 SS ( barrel version), 1/2"-14NPT
|
|
|
|
T
|
|
ANSI 316 SS ( barrel version), M20*1.5(CM20) (To BE USED for WirelessHART)
|
|
|
|
J
|
|
Aluminum alloy ( DIN version), M20*1.5(CM20)
|
Output/Additional options
|
|
|
|
|
7
|
Hart 4-20mA, Standard function-standard functionality
|
|
|
|
|
1
|
Hart 4-20mA, Advanced function-advanced functionality(includes option R1)
|
|
|
|
|
2
|
Profibus PA(includes option R1)
|
|
|
|
|
3
|
Foundation fieldbus(includes option R1)
|
|
|
|
|
8
|
Hart and 4-20mA safety, certified to IEC61058(includes option R1)
|
|
|
|
|
9
|
Wireless Hart(includes option R1)
|
Optional codes
|
/Optional codes
|
|
|
|
|
|